Parameter
6.7.2

Starting frequency and start-time hold function (Pr. 13, Pr. 571)

You can set the starting frequency and hold the set starting frequency for a certain period of time.
Set these functions when you need the starting torque or want to smooth motor drive at a start.
Pr. No. Name
13
Starting frequency
571
Holding time at start
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Starting frequency setting (Pr. 13)
The motor is started with the specified start frequency as soon as the frequency inverter receives a
start signal and a frequency setting that is greater than or equal to the preset starting frequency.
frequency [Hz]
Forward rotation
NOTE
The inverter will not start if the frequency setting signal is less than the value set in Pr. 13.
Example
When 5Hz is set in Pr. 13, the motor will not start running until the frequency setting signal
reaches 5Hz.
m
WARNING:
Note that when Pr. 13 is set to any value lower than Pr. 2 "Minimum frequency", simply turning
on the start signal will run the motor at the preset frequency even if the command frequency is
not input.
FR-E700SC EC
Initial Value
Setting Range
0.5Hz
0–60Hz
0.0–10.0s
9999
9999
Hz
Output
60
Pr.13
0
ON
Description
Frequency at start can be set in the
range 0 to 60Hz.
You can set the starting frequency at
which the start signal is turned on.
Set the holding time of Pr. 13 "Starting
frequency".
Holding function at a start is invalid
Fig. 6-31:
Starting frequency parameter
t
Acceleration and deceleration
Parameters referred to
2 Minimum frequency
Refer to
Section
6.4.1
I000008C
6 - 73