Misoperation prevention and parameter setting restriction
PU stop selection
In any of the PU operation, external operation and network operation modes, the motor can be
stopped by pressing the STOP key of the PU.
When the inverter is stopped by the PU stop function (refer to section 4.3 "Operation panel") in the ex-
ternal operation mode, "PS" is displayed but an alarm is not output. An alarm output is not provided.
After the motor is stopped from the PU, it is necessary to perform PU stop (PS) reset to restart. PS reset
can be made from the unit from which PU stop is made (operation panel, parameter unit (FR-PU04/
PU07, operation panel for FR-E500 (PA02)).
The motor can be restarted by making PS cancel using a power supply reset or RES signal.
When Pr. 75 is set to any of "0 to 3", PU stop (PS display) is invalid, deceleration to a stop by the STOP
key is valid only in the PU operation mode.
NOTE
During operation in the PU operation mode through USB communication or RS-485 communica-
tion from the PU connector, the motor decelerates to stop (PU stop) when STOP is entered from
the operation panel.
6 - 190
Parameter