Inverter Replacement - Mitsubishi Electric FR-E700 Series Instruction Manual

Hide thumbs Also See for FR-E700 Series:
Table of Contents

Advertisement

Inspection
8.1.8

Inverter replacement

The inverter can be replaced with the control circuit wiring kept connected. Before replacement, re-
move the wiring cover of the inverter.
m
WARNING:
● Do not replace the control terminal of the standard control circuit terminal model (inverter
type without "SC") with the control terminal of the safety stop function model (inverter type
"SC"), or vice versa. If replaced by mistake, the inverter does not operate properly.
● Before starting inverter replacement, switch power off, wait for at least 10 minutes, and then
check the voltage with a tester and such to ensure safety.
Remove the installation screw of the control circuit terminal block.
Pull the control circuit terminal downward.
Fig. 8-7:
Using care not to bend the pins of the inverter's control circuit connector, reinstall the control
circuit terminal block and fix it with the installation screw.
Fig. 8-8:
NOTE
Calibration bias and gain changes when changing the control circuit terminal block. Use Pr. 645
and C1 (Pr. 901) to calibrate again in that case.
8 - 10
Removal of the terminal block
Reinstallation of the terminal block
Installation screw
Maintenance and inspection
I002142E
Installation
screw
I002143E