Basic settings
5.1.8

To exhibit the best performance of the motor performance

(offline auto tuning) (Pr. 9, Pr. 71, Pr. 83, Pr. 84, Pr. 96)

The motor performance can be maximized with offline auto tuning.
What is offline auto tuning?
When performing advanced magnetic flux vector control or general-purpose magnetic flux vector
control, the motor can be run with the optimum operating characteristics by automatically measur-
ing the motor constants (offline auto tuning) even when each motor constants differs, other manu-
facturer's motor is used, or the wiring length is long.
Pr.
Name
No.
Electronic thermal
9
O/L relay
71
Applied motor
83
Motor rated voltage
84
Rated motor frequency
96
Auto tuning setting/status
Refer to appendix A for the rated inverter output current.
The initial value differs according to the voltage class: 200V/400V
NOTES
This function is made valid only when a value other than "9999" is set in Pr. 80 and Pr. 81 and
advanced magnetic flux vector control or general-purpose magnetic flux vector control is
selected.)
You can copy the offline auto tuning data (motor constants) to another inverter with the PU
(FR-PU07).
Even when motors (other manufacturer's motor, SF-JRC, etc.) other than Mitsubishi standard
motor, high efficiency motor (SF-JR, SF-HR 0.2kW or more), and Mitsubishi constant-torque motor
(SF-JRCA four-pole, SF-HRCA 0.2kW to 15kW) are used or the wiring length is long, using the offline
auto tuning function runs the motor with the optimum operating characteristics.
Tuning is enabled even when a load is connected to the motor. As the motor may run slightly, fix
the motor securely with a mechanical brake or make sure that there will be no problem in safety if
the motor runs (caution is required especially in elevator). Note that tuning performance is unaf-
fected even if the motor runs slightly.
Reading/writing/copy of motor constants tuned by offline auto tuning are enabled.
The offline auto tuning status can be monitored with the operation panel and PU (FR-PU04/
FR-PU07).
FR-E700SC EC
Initial Value
Setting Range
Rated inverter
0–500A
current
0/1/3–6/ 13–16/ 23/24/40/43/
0
44/50/53/54
0–1000V
200V/400V
50Hz
10–120Hz
0
1
0
11
21
Simple mode parameter list
Description
Set the rated motor current.
By selecting a standard motor or constant-torque motor, thermal charac-
teristic and motor constants of each motor are set.
Set the rated motor voltage (V).
Set the rated motor frequency (Hz).
Offline auto tuning is not performed
Offline auto tuning is performed without motor running
(all motor constants)
For general-purpose magnetic flux vector control
Offline auto tuning is performed without motor running (motor constant
(R1) only)
Offline auto tuning for V/F control
(automatic restart after instantaneous power failure (with frequency
search)) (refer to section 6.12.1)
5 - 15