Mitsubishi Electric FR-E700 Series Instruction Manual page 65

Hide thumbs Also See for FR-E700 Series:
Table of Contents

Advertisement

Wiring
Example
As shown below, always use the start signal (ON or OFF across terminals STF or STR-PC) to make a
start or stop. (Refer to section 6.10.4.)
Fig. 3-23: Example for connection of an inverter
When the power supply is 400V class, install a step-down transformer.
Handling of the inverter output side magnetic contactor
Switch the magnetic contactor between the inverter and motor only when both the inverter and mo-
tor are at a stop. When the magnetic contactor is turned on while the inverter is operating, overcur-
rent protection of the inverter and such will activate. When an MC is provided for switching to the
commercial power supply, for example, switch it on/off after the inverter and motor have stopped.
FR-E700SC EC
Power
supply
Operation preparation
OFF
ON
Start/Stop Operation
Start
Stop
Connection of stand-alone option units
Inverter
T
To the
motor
I001922E
3 - 33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents