Mitsubishi Electric FR-E700 Series Instruction Manual page 284

Hide thumbs Also See for FR-E700 Series:
Table of Contents

Advertisement

Monitor display and monitor output signals
Types of Monitor
Actual operation
time
Motor load factor
Cumulative power
PID set point
PID measured value
PID deviation value
Inverter I/O terminal
monitor
Option input terminal
status
Option output terminal
status
Motor thermal load factor
Inverter thermal load
factor
Tab. 6-35:
Monitor description list (2)
Frequency setting to output terminal status on the PU main monitor are selected by "other
monitor selection" of the parameter unit (FR-PU04/FR-PU07).
The cumulative energization time and actual operation time are accumulated from 0 to 65535
hours, then cleared, and accumulated again from 0.When the operation panel is used, the time is
displayed up to 65.53 (65530h) on the assumption that 1h = 0.001, and thereafter, it is added up
from 0.
Actual operation time is not accumulated when the cumulative operation time is less than 1h until
turning off of the power supply.
When using the parameter unit (FR-PU04/FR-PU07), "kW" is displayed.
Since the panel display of the operation panel is 4 digits in length, the monitor value of more than
"9999" is displayed "----".
Larger thermal value between the motor thermal and transistor thermal is displayed.
A value other than 0% is displayed if the ambient temperature (heatsink temperature) is high even
when the inverter is at a stop.
6 - 140
Pr. 52
Opera-
Unit
tion
PU Main
Panel
Monitor
LED
1h
23
0.1%
24
0.01kWh
25
0.1%
52
0.1%
53
0.1%
54
55
56
57
0.1%
61
0.1%
62
Terminal AM
Pr. 158 (AM)
Full Scale
Setting
Value
24
200%
52
100%
53
100%
Thermal re-
lay opera-
61
tion level
(100%)
Thermal re-
lay opera-
62
tion level
(100%)
Parameter
Description
Adds up and displays the inverter oper-
ation time.
You can check the numbers of the
monitor value exceeded 65535h with
Pr. 564. Can be cleared by Pr. 171. (Refer
to page 6-144.)
Displays the output current value on
the assumption that the inverter rated
current value is 100%.
Monitor value = output power monitor
value/rated inverter current × 100 [%]
Adds up and displays the power
amount based on the output power
monitor.
Can be cleared by Pr. 170.
(Refer to page 6-144.)
Display the set point, measured value
and deviation during PID control.
(Refer to page 6-277 for details.)
Displays the ON/OFF status of the
inverter input terminal and output ter-
minal on the operation panel
(Refer to page 6-143 for details.)
Displays the input terminal ON/OFF sta-
tus of the digital input option
(FR-A7AX-Ekit-SC-E) on the operation
panel. (Refer to page 6-143 for details.)
Displays the output terminal ON/OFF
status of the digital output option
(FR-A7AY-Ekit-SC-E) or relay output
option (FR-A7AR-Ekit-SC-E) on the
operation panel
(Refer to page 6-143 for details.)
Motor thermal heat cumulative value is
displayed.
(Motor overload trip (E.THM) at 100%)
Transistor thermal heat cumulative
value is displayed.
(Inverter overload trip (E.THT) at 100%)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents