X200-X202 DRIVE-CLiQ interfaces

Table 5-3
DRIVE-CLiQ interface X200-X202
PIN
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interface: Fa. Yamaichi, Bestellnummer: Y-ConAS-13
5.3.5

EP terminals X21

Table 5-4
Terminal block X21
Terminal
1
2
2
4
Max. connectable cross-section: 1.5 mm
Type: Screw terminal 1 (see Appendix A)
Note
For operation, 24 V DC must be connected to terminal 3 and ground to terminal 4. When
removed, pulse inhibit is activated (if this has been parameterized).
If the Line Module is not disconnected from the network (e.g. with a main contactor), the DC
link remains charged.
NOTICE
Before the drive line-up is switched off by means of the line disconnecting device, the
voltage at terminals 3 (EP +24 V) and 4 (EP M) must be interrupted. This can be carried out
using a leading breaking auxiliary contact (≥ 10 ms), for example.
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Designation
+Temp
-Temp
EP +24 V (enable pulses)
EP M (enable pulses)
2
Active line modules with cold plate
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
Technical specifications
Temperature sensor connection KTY84–1C130 / PTC
Voltage 24 V DC
Current consumption: 10 mA
Isolated input
Signal propagation times:
L → H: 100 μs
H → L: 1000 μs
5.3 Interface description
115

Advertisement

Table of Contents