Line connection
4.6 Wideband Line Filter for Active Line Modules
4.6.5

Technical Specifications

Table 4-11
Technical data: Wideband Line Filter for Active Line Modules
Rated power
Connection voltages:
Supply voltage
Line frequency
Rated current
Power loss
1
Weight
1 For an overview, see the power loss tables in chapter Cabinet Design
60
6SL3000
0BE21-6AAx 0BE23-
unit
kW
16
V
3-ph. 380 V AC -10 % (-15 % < 1 min) up to 3-ph. 480 V AC +10 %
AC
Hz
47 to 63 Hz
A
30
AC
W
70
kg
8,5
0BE25-
6AAx
5AAx
36
55
67
103
90
110
14,5
15,5
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
0BE28-
0BE31-
0AAx
2AAx
80
120
150
225
150
200
26
34,5