Figure 4-20
Dimension drawing: Basic Line Filter for Smart Line Modules (16 kW and 36 kW)
Table 4-17
Dimensions of Basic Line Filter for Smart Line Modules
Basic Line
Order number
Filter for
Smart Line
Modules
16 kW
6SL3000-0BE21-6DAx
36 kW
6SL3000-0BE23-6DAx
4.8.5

Technical Specifications

Table 4-18
Technical data for: Basic Line Filter for Smart Line Modules
Rated power
Connection voltage:
Supply voltage
Line frequency
Rated current
Power loss
Weight
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
W [mm]
(inches)
429 (16.88)
433 (17.07)
6SL3000-
0HE15-0AAx
Unit
kW
5
V
380 3 AC -10% (-15% < 1 min) to 480 3 AC +10%
AC
Hz
47 to 63 Hz
A
16
AC
W
20
kg
2,1
4.8 Basic Line Filter for Smart Line Modules
b [mm]
a [mm]
(inches)
(inches)
50 (1.96)
15 (0.59)
75 (2.95)
15 (0.59)
0HE21-0AAx
0BE21-6DAx
10
16
25
36
20
16
2,3
5
Line connection
H [mm]
h [mm]
(inches)
(inches)
156 (6.14)
31 (1.22)
135 (5.31)
68 (2.67)
0BE23-6DAx
36
65
28
6,5