If, at the lefthand end of the drive line-up, there is a 50 mm wide Motor Module or a DC link
component of the appropriate width (e.g. Braking Module, CSM, VCM), then the DC link
bridge and all of the associated screws must be removed completely. It is not permissible to
insert the screws without a DC link bridge.
For all other power units and DC link components (e.g. Capacitor Module) that are wider
than 50 mm, the DC link bridge must be moved as far as possible to the right and secured
with screws; it must not be moved to the left or removed.
If this is not carefully observed, this can result in damage and accidents.
CAUTION
The total length of the power cables (motor supply cables and DC link cables) must not
exceed 350 m in active mode.
The total length of the power cables (motor supply cables and DC link cables) must not
exceed 1000 m in active mode in conjunction with the Active Interface Module and Basic
Line Filter.
CAUTION
Only Siemens cables may be used for DRIVE-CLiQ connections.
CAUTION
The DC link peripheral covers are supplied as standard with the components; they can also
be ordered separately, if required (order no.: 6SL3162-5AA00-0AA0).
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
DANGER
Active line modules with cold plate
5.2 Safety information