Line connection
4.4 Basic Line Filter for Active Line Modules with line reactor
4.4.5

Technical Specifications

Table 4-4
Technical data of Basic Line Filter for Active Line Modules with line reactor
Rated power
Connection voltage:
Supply voltage
Line frequency
Rated current
Power loss
1
Weight
1 For an overview, see the power loss tables in Cabinet Design.
44
6SL3000
unit
kW
V
AC
Hz
A
AC
W
kg
0BE21-6DAx
0BE23-6DAx
16
36
380 3 AC -10% (-15% < 1 min) to 480 3 AC +10%
47 to 63 Hz
36
65
16
28
5
6,5
0BE25-5DAx
55
105
41
11,5