Power components on the motor side
12.1 Motor reactors
12.1.2
Safety information
A ventilation clearance of 100 mm above and below the components must be observed.
Note
The connecting cables to the Motor Module must be kept as short as possible (max. 5 m).
CAUTION
When using motor reactors that SIEMENS has not approved for SINAMICS, then these can
thermally damage the reactor.
The surface temperature of the motor reactors can exceed 80 °C.
CAUTION
The maximum permissible output frequency when motor reactors are used is 120 Hz.
250
WARNING
CAUTION
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4