Installation - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

6.5

Installation

Mounting the cold plate component on customer-specific heat sinks
Note the following before installation:
● Before mounting, check the surface of the heat sink to ensure that it is not damaged.
● To facilitate installation, M6 screw bolts and hexagon nuts/threaded pins (ISO 7436-
● To improve heat transfer, a heat-conducting medium must be used. Special spherical-
Heat-conducting foil, 50 mm
Heat-conducting foil, 100 mm
Heat-conducting foil, 150 mm
Heat-conducting foil, 200 mm
Heat-conducting foil, 300 mm
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
M6x40-14 H, strength class 8.8) are recommended.
indented heat-conducting film must be used for this purpose. Every cold plate power unit
is supplied with heat-conducting film cut to the right size. Note the installation position of
the heat-conducting film (see diagrams below).
Note
When a component is replaced, the heat-conducting film must also be replaced! Only
heat-conducting film approved or supplied by Siemens may be used.
Basic Line Modules with cold plate
Order No.
6SL3162-6FB00-0AA0
6SL3162-6FD00-0AA0
6SL3162-6FF00-0AA0
6SL3162-6FH00-0AA0
6SL3162-6FM00-0AA0
6.5 Installation
143

Advertisement

Table of Contents
loading

Table of Contents