13.2 DC link rectifier adapter
13.2.5

Installation

If a 50 mm wide component or if a DC link component with the appropriate width (e.g.
Braking Module, CSM, VCM) is located on the left-hand side of the drive line-up, the DC
link bridge including all of the screws must be removed. The screws must not be inserted
without a DC link bridge.
For all other power units and DC link components (e.g. Capacitor Module) that are wider
than 50 mm, it is not permissible to remove the DC link bridge.
If this is not carefully observed, this can result in damage and accidents.
Required tools:
● Flat-bladed screwdriver 1 (0.5 x 3.5)
● Torx screwdriver T10
● Torx screwdriver T20
276
DANGER
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4