The line filters listed conduct a high leakage current via the PE conductor. A permanent PE
connection for the line filter or control cabinet is required due to the high leakage current of
the line filters.
Furthermore, the following measures must be taken according to EN 61800-5-1:
Either protective ground conductor cross-sections ≥ 10 mm
protective ground conductor of the same cross-section as the first one.
Risk of electric shock. Dangerous voltages are still present for up to 5 minutes after the
power supply has been switched off.
Note
If a high-voltage test is conducted with alternating voltage in the system, the line filters must
be disconnected in order to obtain accurate measurements.
CAUTION
Only the line filters described in this Manual must be used. Other line filters can cause line
harmonics that can interfere with or damage other loads powered from the line supply.
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
DANGER
DANGER
4.4 Basic Line Filter for Active Line Modules with line reactor
Line connection