Installing the Cold-Plate Modules on Customer-Specific Heat Sinks

Mounting the cold plate component on customer-specific heat sinks
Note the following before installation:
● Before mounting, check the surface of the heat sink to ensure that it is not damaged.
● To facilitate installation, M6 screw bolts and hexagon nuts/threaded pins (ISO 7436-
● To improve heat transfer, a heat-conducting medium must be used. Special spherical-
Heat-conducting foil, 50 mm
Heat-conducting foil, 100 mm
Heat-conducting foil, 150 mm
Heat-conducting foil, 200 mm
Heat-conducting foil, 300 mm
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
5.5 Installing the Cold-Plate Modules on Customer-Specific Heat Sinks
M6x40-14 H, strength class 8.8) are recommended.
indented heat-conducting film must be used for this purpose. Every cold plate power unit
is supplied with heat-conducting film cut to the right size. Note the installation position of
the heat-conducting film (see diagram below).
Note
When a component is replaced, the heat-conducting film must also be replaced.
Only heat-conducting film approved or supplied by Siemens can be used.