Installation - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Accessories
13.3 DC link adapter
13.3.5

Installation

If a 50 mm wide module or if a DC link component with the appropriate width (e.g. Braking
Module, Control Supply Module, Voltage Clamping Module) is located at the left-hand end
of the drive line-up, then the DC link bridge including all of the screws must be removed.
The screws must not be inserted without a DC link bridge.
For all other power units and DC link components (e.g. Capacitor Module) that are wider
than 50 mm, it is not permissible to remove the DC link bridge.
If this is not carefully observed, this can result in damage and accidents.
Required tools:
● Torx screwdriver T20
● Flat-bladed screwdriver 1 (0.5 – 3.5)
286
DANGER
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4