Siemens SINAMICS S120 Equipment Manual page 325

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

The cable shields must be connected as close to the conductor terminal connections as
possible to ensure a low-impedance connection with cabinet ground. For Siemens power
cables in which the shield is connected to the connector shell (see relevant catalog), this is a
sufficiently good shield contact.
With components that do not have any special shield connection or where the shield
connection is not sufficient, the cable shields can be connected to the metal mounting plate
using hose clamps and toothed rails. The cable length between the shield contact point and
the terminals for cable conductors must be kept as short as possible.
Shield contact plates with pre-prepared clip contacts are available for contacting the shields
for power cables of Line Modules and Motor Modules. Up to a module width of 100 mm,
these plates are part of the scope of supply of the components, or they are integrated in the
connector.
All cables inside the cabinet must be connected as closely as possible to parts connected
with cabinet ground, such as a mounting plate or cabinet wall. Ducts made of sheet steel or
routing cables between between steel sheets (e.g. between the mounting plate and back
wall) should provide adequate shielding.
Avoid, where possible, routing unshielded cables, connected to the drive line-up, in the
immediate vicinity of noise sources, e.g. transformers. Signal lines (shielded and unshielded)
connected to the drive line-up, must be routed as far as possible away from strong external
magnetic fields (e.g. transformers, line reactors). In both cases, a distance of ≥ 300 mm is
usually sufficient.
The Voltage Clamping Module conducts a high leakage current via the functional ground.
This means that a permanent PE connection must be provided for the cabinet (PE) rail.
Other than that the following measures must be taken in accordance with EN 61800-5-1:
Either protective ground conductor cross-sections ≥ 10 mm
protective ground conductor of the same cross-section as the first one.
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
DANGER
Cabinet Design and EMC
14.5 Electromagnetic Compatibility
Cu or installation of a second