Problems With Mains Operation - Display - Kessel Staufix FKA Standard Installation And Operating Manual

Control unit/electric components for automatic backwater valve for wastewater containing sewage
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 25
8. Problems with mains operation of Comfort control unit
8.2 Problems with mains operation / display
Display
Cause
Remedy
Remove
Battery is missing or
connect batteries, replace by
faulty
new batteries if necessary
"Battery fault"
When the unit is ready to func-
tion, a running light appears on
the display again.
- Initialisation:
Remove the mains plug, dis-
"Motor" control cable
connect the battery; check the
is not connected,
control
connected with inver-
connection or passage, replace
se polarity or is broken
motor if necessary.
- During operation:
"motor" control cable
faulty
"Motor fault"
- Initialisation: "Probe"
Remove the mains plug, deac-
control cable is not
tivate the battery; check the
connected, connected
control
with inverse polarity or
connection or passage, replace
is broken
probe if necessary.
- During operation:
"Probe" control cable
faulty
"Probe faulty"
Remove the mains plug, deac-
Flap cannot be closed
tivate the battery, open the
completely
during
Staufix
start-up or by the
blockage and return to operati-
"test" key, i.e. the flap
on
is blocked by an ob-
Recommendation:
ject in the backwater
Inform a specialist company
flap "Flap fault"
- See installation instructions
- Wrong lever position
010-842 (section 4.2.1)
during cover fitting
Close the emergency valve.
Backwater detected.
After the end of backwater, re-
The flap cannot be clo-
move the blockage as descri-
sed completely, howe-
bed
ver, i.e. it is blocked by
an object, "Flap fault
during backwater"
Max. number of cy-
Replace motor
cles for flap exceeded
Motor transmitting fi-
Inform the customer service
gure exceeded
partner
the
mains
plug,
cable
for
correct
cable
for
correct
cover, eliminate the
43
Notes
- Initialisation: The system can be
put into operation, i.e. it is functional.
Alarm can be acknowledged.
- Operation: The fault message ap-
pears after a maximum of 5 minutes.
The system is ready for operation,
manual mode is possible.
Fault detection only takes place du-
ring operation (see chapter 8.2 "Addi-
tional functions").
- Initialisation: Cannot be put into
operation
- During operation: Fault detection
during
manual
operation
cycle/backwater
The probe is scanned every 2 se-
conds.
Caution: Check position of the ope-
rating valve! The control attempts to
close the flap 3 x in the interval and
perhaps eliminate the blocking ob-
ject in the process. If the object can
be removed by the flap movement
during these cycles, the system is
ready to be used again. If this does
not work, the system switches to
fault. Acknowledgement of the acou-
stic signal is possible. It is also pos-
sible to remove the object by flushing
the line. This can be checked by
pressing the test key again. In the
event of a negative result, the fault
message appears again; the object
must be removed as described
under remedial measures.
Motor service life reached
Flap closes too often within a short
time
test