This chapter describes the specifications of the C Controller module.
3.1

General Specifications

The following indicates the general specifications.
Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Vibration resistance
Shock resistance
Operating
atmosphere
*3
Operating altitude
Installation location
Overvoltage
*4
category
*5
Pollution degree
Device class
*1 :
The storage ambient temperature is -20 to 75°C if the system includes an AnS series module.
*2 :
The operating ambient humidity and storage ambient humidity are 10 to 90%RH if the system includes an AnS series
module.
*3 :
Do not use or store the C Controller module under pressure higher than the atmospheric pressure at sea level.
Doing so can cause malfunction.For use in a pressurized environment, please consult your local Mitsubishi representative.
*4 :
This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises. Category II applies to equipment for which electrical
power is supplied from fixed facilities.surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*5 :
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used.Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by
condensing must be expected occasionally.
Remark
To install/connect peripherals to the C Controller module, the specifications of both the C Controller module and peripherals
should be satisfied.
44
SPECIFICATIONS
Under
Compliant with
intermittent
JIS B 3502 and
vibration
IEC 61131-2
Under continuous
vibration
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
Specifications
0 to 55°C
*1
-25 to 75°C
5 to 95%RH, non-condensing
Constant
Frequency
acceleration
5 to 8.4Hz
8.4 to 150Hz
9.8m/s
5 to 8.4Hz
8.4 to 150Hz
4.9m/s
2
, 3 times each in 3 directions X, Y, Z)
No corrosive gases
0 to 2000m
Inside a control panel
II or less
2 or less
Class I
*2
Half
Sweep count
amplitude
3.5mm
10 times
each in X, Y
2
directions
1.75mm
2
and Z

Advertisement