Starting the drive system after an emergency-off

1. To start the drive system after an emergency-off, unlatch the
EMERGENCY-OFF push button.
The EMERGENCY-OFF push button returns to its initial position when
turned into the direction indicated by the arrows on the push button.
2. Press the EMERGENCY-OFF RESET button to reset the emergency-off
safety relay of the drive.
• The drive remains in emergency-off state until the DC-link voltage
has dropped to < 50 V (discharged).
• After resetting, the status message of the drive changes to "Ready
to switch on".
3. The main power supply can be connected to the drive again and the
drive system can be started up.