Readers
5.4 SIMATIC RF680R
5.4.1.6

Pin assignment of the Industrial Ethernet interface (X1 P1; X1 P2)

Table 5- 29
Interface view
(M12 connector, 4-pin, D coding, wiring end)
5.4.1.7

Grounding connection

On the top of the reader there is a blind drill hole (M4 x 8) for grounding. Tighten the screw
with a torque of ≃ 1.5 Nm.
Hazardous voltage due to lightning strikes
Death or serious injury may occur as a result of lightning strikes to antennas mounted
outside buildings.
If the reader is operated with antennas mounted outside buildings, it is imperative that the
reader is electrically connected to the ground potential.
NOTICE
Installation only in protected areas
The antenna can be installed in the protected part of a building. When implementing your
lightning protection concept, make sure you adhere to the VDE 0182 or IEC 62305
standards.
154
Pin assignment of the Industrial Ethernet interface
WARNING
Pin
Pin assignment
1
Data line TxP
2
Data line RxP
3
Data line TxN
4
Data line RxN
System Manual, 11/2018, J31069-D0171-U001-A21-7618
SIMATIC RF600