Mounting Sequence - WAGO 750-486 Manual

4ai 0/4-20 ma, ex i, 4-channel analog input, 0/4-20 ma, namur ne43, ex i for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-486 4AI 0/4-20 mA, Ex i
5.1

Mounting Sequence

Fieldbus couplers, controllers and I/O modules of the WAGO I/O SYSTEM 750
are snapped directly on a carrier rail in accordance with the European standard
EN 60175 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual devices are securely seated
on the rail after installation.
Starting with the fieldbus coupler or controller, the I/O modules are mounted
adjacent to each other according to the project design. Errors in the design of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the I/O modules with power contacts (blade contacts) cannot be
linked to I/O modules with fewer power contacts.
Insert I/O modules only from the proper direction!
All I/O modules feature grooves for power jumper contacts on the right side. For
some I/O modules, the grooves are closed on the top. Therefore, I/O modules
featuring a power jumper contact on the left side cannot be snapped from the
top. This mechanical coding helps to avoid configuration errors, which may
destroy the I/O modules. Therefore, insert I/O modules only from the right and
from the top.
Requirements for Clearances and Creepage Distances
For all sections of a node that contain I/O modules for Ex-i use, stricter require-
ments with regard to clearances and creepage distances apply.
Before such a node section, the respective Ex i supply module (750-606
or 750-625/000-001) ensures the required distance.
After such a node section, 4 distance modules (750-616) must be used.
Exceptions: If the following section consists of:
an end module for internal bus extension (750-627), 1 distance
module (750-616) is sufficient;
an end module (750-600), no distance modules are required.
Don't forget the bus end module!
Always plug a bus end module (750-600) onto the end of the fieldbus node! You
must always use a bus end module at all fieldbus nodes with WAGO I/O
SYSTEM 750 fieldbus couplers or controllers to guarantee proper data transfer.
Mounting
43
Manual
Version 1.1.2

Advertisement

Table of Contents
loading

Table of Contents