Cage Clamp; Figure 4: Cage Clamp ® Connections; Table 7: Legend For "Cage Clamp ® Connections" Figure - WAGO 750-486 Manual

4ai 0/4-20 ma, ex i, 4-channel analog input, 0/4-20 ma, namur ne43, ex i for wago-i/o-system 750
Table of Contents

Advertisement

22
Device Description
3.2.3

CAGE CLAMP

Figure 4: CAGE CLAMP
Table 7: Legend for "CAGE CLAMP
Chann
el
1
2
3
4
Use shielded signal lines!
Only use shielded signal lines for analog signals and I/O modules which are
equipped with shield clamps. Only then can you ensure that the accuracy and
interference immunity specified for the respective I/O module can be achieved
even in the presence of interference acting on the signal cable.
Manual
Version 1.1.2
®
Connectors
®
Connections
®
Connections" Figure
Designation
Connectio
n
Uv 1
1
0 V
2
AI 1
3
S
4
Uv 2
5
0 V
6
AI 2
7
S
8
Uv 3
9
0 V
10
AI 3
11
S
12
Uv 4
13
0 V
14
AI 4
15
S
16
WAGO-I/O-SYSTEM 750
750-486 4AI 0/4-20 mA, Ex i
Function
Input AI 1: Sensor supply Uv
Input AI 1: Sensor supply 0 V
Input AI 1: Signal voltage
Input AI 1: Shield connection
Input AI 2: Sensor supply Uv
Input AI 2: Sensor supply 0 V
Input AI 2: Signal voltage
Input AI 2: Shield connection
Input AI 3: Sensor supply Uv
Input AI 3: Sensor supply 0 V
Input AI 3: Signal voltage
Input AI 3: Shield connection
Input AI 4: Sensor supply Uv
Input AI 4: Sensor supply 0 V
Input AI 4: Signal voltage
Input AI 4: Shield connection