Process Image
4.3.2.3

Sensor Type 3.6-21 mA (Namur NE43)

For the current measurement with sensor type 3.6-21 mA, the input range of
+3.6 mA ... +21 mA is mapped to a value rage of −765 ... +32763. The current
underranges and overranges refer to manufacturer range violations.
Table 23: Process Image, Sensor Type 3.6-21 mA (NAMUR NE43), Two's Complement
Representation
Input current
mA
< 1.0
Wire break
< 3.6
Underrange
3.6
3.8
4.0
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
20.0
20.5
21.0
Overrange
> 21.0
Short circuit
> 21.0
1)
Status bits: X: not used, F= error, Ü= overflow
2)
When underrange / overrange limit is ON
3)
When wire break / short circuit diagnostics is ON
Manual
Version 1.1.2
Numeric value
Binary
'1111.1100.1111.1 011'
3)
'1111.1100.1111.1 011'
2)
'1111.1100.1111.1 011'
'1111.1110.0111.1 000'
'0000.0000.0000.0 000'
'0000.1100.0000.1 000'
'0001.1000.0001.0 000'
'0010.0100.0010.0 000'
'0011.0000.0010.1 000'
'0011.1100.0011.1 000'
'0100.1000.0100.0 000'
'0101.0100.0101.0 000'
'0110.0000.0101.1 000'
'0111.0000.0110.1 000'
'0111.1000.1110.0 000'
'0111.1100.0011.1 000'
'0111.1111.1111.1 011'
2)
'0111.1111.1111.1 011'
3)
'0111.1111.1111.1 011'
750-486 4AI 0/4-20 mA, Ex i
1)
XFÜ
Hex.
Dec.
0xFCFB
−765
0xFCFB
−765
0xFCFB
−765
0xFE78
−392
0x0000
0
0x0C08
3080
0x1810
6160
0x2420
9248
0x3028
12328
0x3C38
15416
0x4840
18496
0x5450
21584
0x6058
24664
0x6C68
27752
0x7870
30832
0x7C38
31800
0x7FFB
32763
0x7FFB
32763
0x7FFB
32763
WAGO-I/O-SYSTEM 750
Status
Byte
Error LED
Hex.
0x60
ON
0x41
ON
0x41
ON
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON
0x42
ON
0x50
ON