Special Format; Sensor Type 0-20 Ma; Table 24: Process Image, Sensor Type 0-20 Ma, Amount/Sign Format - WAGO 750-486 Manual

4ai 0/4-20 ma, ex i, 4-channel analog input, 0/4-20 ma, namur ne43, ex i for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-486 4AI 0/4-20 mA, Ex i
4.3.3

Special Format

4.3.3.1

Sensor Type 0-20 mA

For the current measurement with sensor type 0-20 mA, the input range of
0 mA ... +20 mA is mapped to a process value rage of 0 ... +32763. The current
underranges and overranges refer to manufacturer range violations.

Table 24: Process Image, Sensor Type 0-20 mA, Amount/Sign Format

Input current
mA
< 0
Underrange
0.0
2.5
5.0
7.5
10.0
12.5
15.0
17.5
20.0
Overrange
> 20.0
Short circuit
> 21.0
1)
Status bits: X: not used, F= error, Ü= overflow
2)
When underrange / overrange limit is ON
3)
When short circuit diagnostics is ON
Numeric value
Binary
'0000.0000.0000.0 011'
2)
'0000.0000.0000.0 000'
'0000.1111.1111.1 000'
'0001.1111.1111.1 000'
'0010.1111.1111.1 000'
'0011.1111.1111.1 000'
'0100.1111.1111.1 000'
'0101.1111.1111.1 000'
'0110.1111.1111.1 000'
'0111.1111.1111.1 000'
2)
'0111.1111.1111.1 011'
3)
'0111.1111.1111.1 011'
1)
XFÜ
Hex.
Dec.
0x0003
3
0x0000
0
0x0FF8
4088
0x1FF8
8184
0x2FF8
12280
0x3FF8
16376
0x4FF8
20472
0x5FF8
24568
0x6FF8
28664
0x7FF8
32760
0x7FFB
32763
0x7FFB
32763
Process Image
39
Status
Byte
Error LED
Hex.
0x41
ON
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON
0x50
ON
Manual
Version 1.1.2

Advertisement

Table of Contents
loading