Commissioning

Table 38: Calibration Menu Item

Option
Selection
of the
calibration
method
A/D raw value
Current [mA]
*)
Factory setting
Manual
Version 1.1.2
Description
Activate factory configuration
*)
Activate
calibration is activated.
factory
Gain
calibration.
Offset
Activate user calibration
*)
calibration is activated.
Activate user
Gain
calibration
Offset
Raw value of the analog/digital converter. This is a
14-bit value.
If the channel is deactivated, "N/A" (not available) is
displayed.
The A/D raw value is read cyclically from the I/O
module.
Display of the calibrated input current in milliamps
(mA).
This is a 32-bit value.
If the channel is deactivated, "N/A" (not available) is
displayed.
The input current value is read cyclically from the I/O
module.
750-486 4AI 0/4-20 mA, Ex i
Factory calibration is activated and user
calibration is deactivated.
Factory calibration is deactivated and user
The Gain value is specified by the
manufacturer.
The Offset value is specified by the
manufacturer.
User calibration is activated and factory
calibration is deactivated.
You determine the gain and offset value
yourself.
User calibration is deactivated and factory
Enter the Gain value for the user calibration.
The Gain value changes the gain factor of the
A/D raw value.
The value entered must fall within the value
range 0 ... 65535.
The resolution is 1/8192.
Enter the Offset value for the user calibration.
The Offset value moves the zero point of the
A/D raw value (offset on the y axis).
The value entered must fall within the value
range −32768 ... 32767.