Table 22: Output Byte D0 (Enable Sensor Type Nc) - WAGO 750-439 Manual

8-channel digital input module namur, ex i, proximity sensor acc. to en 60947-5-6 for wago-i/o-system 750
Table of Contents

Advertisement

32
Process Image
Output byte D0 is used to determine whether a make contact or a break contact
should be processed as sensor.

Table 22: Output Byte D0 (Enable Sensor Type NC)

Bit 7
NC_ENA
8
NC_ENA1
NC_ENA2
NC_ENA3
NC_ENA4
NC_ENA5
NC_ENA6
NC_ENA7
NC_ENA8
Legend
ENA: "enabled"
NC: Break contact ("Normally Closed")
NO: Make contact ("Normally Open")
Output byte D1 is used to determine channel by channel whether diagnostics
should be evaluated.
If only one contact is to be monitored instead of a NAMUR sensor, for example,
the respective LED diagnostics can be switched off using output byte D1.
Manual
Version 1.3.0, valid from HW Version 03, SW Version 03
Bit 6
Bit 5
NC_ENA
NC_ENA
NC_ENA
7
6
Sensor type IN1
0:
NO
1:
NC
Sensor type IN2
0:
NO
1:
NC
Sensor type IN3
0:
NO
1:
NC
Sensor type IN4
0:
NO
1:
NC
Sensor type IN5
0:
NO
1:
NC
Sensor type IN6
0:
NO
1:
NC
Sensor type IN7
0:
NO
1:
NC
Sensor type IN8
0:
NO
1:
NC
Bit 4
Bit 3
Bit 2
NC_ENA
NC_ENA
5
4
WAGO-I/O-SYSTEM 750
750-439 8DI NAMUR Ex i
Bit 1
Bit 0
NC_ENA
NC_ENA
3
2
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

8di namur ex i