Safety instrumented systems requirements
April 2020
Design the loop so that the terminal voltage does not drop below 10.5 Vdc when the
transmitter output is set to 23 mA. For more information see the
Product Data
Position the security switch to the ( ) position to prevent accidental or deliberate change
of configuration data during normal operation.
7.4
Configuring in safety instrumented systems
(SIS) applications
Use any HART
of the Rosemount 3051P.
Note
Transmitter output is not safety-rated during the following: configuration changes,
multidrop, and loop test. Use alternative means to ensure process safety during
transmitter configuration and maintenance activities.
7.4.1
Damping
User-selected damping will affect the transmitters ability to respond to changes in the
applied process. The damping value and response time must not exceed the loop
requirements.
Reference
92
Sheet.
®
capable configuration tool to communicate with and verify configuration
Damping
to change damping value.