Wilo Control EC-Booster Installation And Operating Instructions Manual page 70

Hide thumbs Also See for Control EC-Booster:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 47
en
Fig. 31: Menu 5.11
Fig. 32: Menu 5.14
Fig. 33: Menu 5.15
Fig. 34: Menu 5.16
Fig. 35: Menu 5.40
Fig. 36: Menu 5.41
Fig. 37: Menu 5.42
70
Commissioning
Menu no.
5.11
Description
Pressure sensor measurement range
Value range
1 ... 25 bar
Factory setting
16 bar
Menu no.
5.14 (Control ECe-Booster only)
Description
PID controller: Proportional factor
Value range
0.1 ... 100
Factory setting
2.5
Explanation
Menu no.
5.15 (Control ECe-Booster only)
Description
PID controller: Integral factor
Value range
0 ... 300
Factory setting
0.5
Explanation
Menu no.
5.16 (Control ECe-Booster only)
Description
PID controller: Differential factor
Value range
0 ... 300
Factory setting
0
Explanation
Menu no.
5.40
Description
Switch "pump kick" function On/Off
Value range
off, on
Factory setting
on
Menu no.
5.41
Description
Allows "pump kick" when status is Extern OFF
Value range
off, on
Factory setting
on
Menu no.
5.42
Description
"Pump kick" interval
Value range
1 ... 336 h
Factory setting
24 h