USE AND MAINTENANCE MANUAL – DLC
Table 7. Serial port parameters for communication with Logic DLC3-RD
Parameter
Transmission
Baud rate
Word
Stop bit
Parity
3.6.3
RS-485 connection
with display BEKA
BA488C
Table 8. Connection with remote display for safe area BEKA
Terminal
TB3-1
TB3-2
TB3-3
Figure 17. Connection of DLC
LOGIC S.r.l. - M0145Db.docx
Mod. L0006A01 of 30/05/2016
NET
Series
Below are listed the serial configuration parameters for communication with
NET
DLC
. These parameters are already set on both instruments, with no need for
any settings:
Value
Asynchronous
19200
8 bits
1
None
®
The connection with the remote display BEKA
be through the BEKA
settings of the remote display to be set for correct operation are shown in Figure
17.
The shield must be connected at one point only, cabinet side (DLC
better immunity to low frequency noise (ground loop).
Connection
GND / Shield
T
- / R
-
XA
XA
T
+ / R
+
XA
XA
NET
®
to display BEKA
BA488C
®
BA201 barrier, as shown in Table 8 and in Figure 17. The
®
BA488C
®
BA488C in hazardous area must
Installation
NET
), for
Page 26 of 78