Diagnostics
8.8

LED "H" Status Diagnosis

LED "H" provides information about
whether the latching relay function is enabled,
where there is a short circuit of the DALI power supply:

Table 35: LED "H" Status Diagnosis

Status
Off
Green
Green
flashing
Red
See also Section "LEDs A-H Flashing Together"
*)
Short circuit detection only with WAGO power supply
A short circuit on the DALI line is only detected if the 18 V power is supplied via a
WAGO power supply (item no.: 787-1007 or item no. 753-620).
For this purpose, the "Enable Internal Power Supply" box must be checked (see
section "Module Configuration Notes").
If an external DALI power supply is used, it is not possible to distinguish between
"short circuit" and "voltage not present."
8.9

LEDs A-H Flashing Together

With DALI-2, HW 03/FW 20 or higher, the "Identification" function can be used in
which all display elements of the DALI Multi-Master Module flash green for
approx. 10 sec. This "Wink Function" can be used to identify the affected module
in the node.
Manual
Version 1.4.3
Explanation
Latching relay function is
switched off.
Latching relay function is
switched on.
"Identification" function is
enabled.
*)
There is a short circuit on the
DALI line.
WAGO-I/O-SYSTEM 750
753-647 DALI Multi-Master
Additional Information
Only in "easy mode." The WAGO
DALI Configurator is used to switch to
the latching relay mode; see section
"Latching Relay Function."
The 18 V power supply of the I/O
module is present, the internal power
supply is enabled and the DALI
voltage is not present.