Connection Type; Climatic Environmental Conditions; Table 13: Technical Data - Field Wiring; Table 14: Technical Data - Data Contacts - WAGO 750 Series Manual

Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
753-647 DALI Multi-Master
3.9.4

Connection Type

Table 13: Technical Data – Field Wiring
Wire connection
Cross section
Stripped lengths
Table 14: Technical Data – Data Contacts
Data contacts
3.9.5

Climatic Environmental Conditions

Table 15: Technical Data – Climatic Environmental Conditions
Surrounding air temperature, operation 0 °C ... 55 °C
Surrounding air temperature, storage
Operating altitude
Relative humidity
Pollution degree
Protection type
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
Device Description
CAGE CLAMP
®
0.08 mm² ... 2.5 mm², AWG 28 ... 14
8 mm ... 9 mm / 0.33 in
Slide contact, hard gold plated, self-
cleaning
−25 °C ... +85 °C
0 ... 2000 m
Max. 5 % ... 95 % without condensation
2
IP20
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
Ensure that additional measures for
components are taken, which are used
in an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
31