Clear All; Examples - ProMinent DULCO flex Control-DFYa Operating Instructions Manual

Peristaltic metering pump
Table of Contents

Advertisement

12.4.3

Clear all

12.4.4

Examples

Example of "Weekday metering"
Tab. 11: Program as program lines / instructions
No.
Time event
01
workdays 1 (Mo-
Fr)
02
workdays 1 (Mo-
Fr)
03
workdays 1 (Mo-
Fr)
04
workdays 1 (Mo-
Fr)
05
workdays 1 (Mo-
Fr)
06
workdays 1 (Mo-
Fr)
How to enter the program lines / instruc‐
tions:
'Menu / Information è Timer è Clear all è ...'
'Clear all' menu to clear all instructions (the entire program).
Use the
Requirements:
You have already worked with the pump type
n
The time has been set (possibly set under
n
Time' . Only possible with 'Timer status' - 'Inactive' ).
è
Task:
The pump is to meter 2 litres every half hour every weekday (Mon-Fri)
between 8:00 and 11:00.
Solution:
As you define switching times with the timer, you need to first define the
switching points at 08:30, 09:30 and 10:30.
To meter 2 litres, the pump needs to work in
'Dos. capacity' of 12,000 l/h. A 'Dos. capacity' of 12,000
for 10 min at a
l/h is thereby added to the switching points.
You also need to define the switching times to stop the pump at 08:40,
09:40 and 10:40 - paired with the
Action
Switching time
08:30
Manual
08:40
Stop
09:30
Manual
09:40
Stop
10:30
Manual
10:40
Stop
1.
To program the timer, set
Activation' to 'inactive' .
è
ð The first line of the timer menu
'Inactive' .
2.
Always enter the program / instructions from the table, above, into
the newly created instruction under
...' (Do not get irritated: the timer program automatically sorts
è
the instructions).
3.
To activate the timer, set
ð The first line of the timer menu
'active' .
The timer starts working - the timer identifier
continuous display.
Set up /
'Settings è Set time
'Manual' 'operating mode'
'Halt' action.
Comment
Capacity
12,000 l/h
Meter at 12,000
l/h
-
Stop
12,000 l/h
Meter at 12,000
l/h
-
Stop
12,000 l/h
Meter at 12,000
l/h
-
Stop
'Menu / Information è Timer
'Timer status' then shows
'Timer è Set timer è new
'Activation' to 'active' .
'Timer status' then displays
is visible in the
'Menu'
63

Advertisement

Table of Contents
loading

Table of Contents