Advertisement

5. Maintenance and conversion

5.4 Conversion work on the CPA valve terminal

5.4.1 Conversion from pushing to pushing/locking manual override

CPA... 9808A
The following conversion work can be undertaken on
the CPA valve terminal:
– Conversion to pushing or locking manual override on
CPA valve terminals with MP, CP or AS-i connection.
– Conversion of the CPA valve terminal to internal or
external pilot air.
– Conversion of the CPA valve terminal to different
pressure zones.
– Conversion to single or double solenoid valve
locations.
You can convert CPA valve terminals with MP, CP or
AS-i connection from pushing to pushing/locking ma-
nual override by removing the locking clip.
The manual overrides on CPA valve terminals with IC
connection can be actuated in both pushing and locking
form. Conversion is not necessary.
Proceed as follows:
If you wish to re-use the locking clip:
• use a thin object (e.g. a spatula) to lift the locking
clip out of its fixing (see Fig. 5/10,

).
5-17