Locating Faults - Festo CPA VI Series Manual

Compact performance valve terminal pneumatics
Hide thumbs Also See for CPA VI Series:
Table of Contents

Advertisement

4. Commissioning

4.2 Locating faults

Operating status of the
pneumatic system
Air comes out...
– at common line
connections
– at work line
connections
– between the modules
Valve or pneumatic system
– does not react as expected
– does not react
– does not react
CPA... 9808A
Malfunctioning
When you switch on the compressed air supply or test
the individual valves, you can learn the following about
the operating status of the pneumtic system:
Valve position
– Basic position
– Switch position
– Basic position
– Switch position
– Switch position
– Switch position
Error treatment when compressed
air supply has beeen switched off
• Check the tubing
• Check the tubing
• After switching on, regulate
external pilot air to 3 to 8 bar
• Check tubing
• After switching on,
check operating pressure
(e.g. pressure zones)
• Place locking manual override in
basic position
• In the case of CPA valve terminals
with 3/2-way valves, check external
pilot air (or set as a factor of
working pressure)
• Servicing required
• Check regulator (apply pressure
>3 bar to regulator )
4-11