5. Maintenance and conversion
5.4.2 Conversion to internal or external pilot air
Right hand end plate
for internal pilot air:
for external pilot air:
Fig. 5/3: Right hand end plate
CPA... 9808A
By fitting the appropriate right hand end plate, you can
convert your CPA valve terminal to internal or external
pilot air.
PLEASE NOTE
Mixed operation of the CPA valve terminal with inter-
nal and external pilot air is not intended. The sub-
base for separation of the pressure zones does not
divide the auxiliary pilot air channel.
The available right hand end plates are listed in the
table below. Check whether the right hand end plate is
intended for internal or external pilot air.
Description
Connection 12/14 in right hand end plate is not marked
and is sealed with a blind plug. The auxiliary pilot air is
taken internally from connection 1. Separation of
pressure zones is permitted.
Non-required connections must be sealed.
Connection 12/14 in right hand end plate for
connecting the auxiliary pilot air is marked.
Separation of pressure zones is permitted.
Non-required connections must be sealed.
How you should fit the appropriate end plate into your
CPA valve terminal is described under "Replacing the
end plate, sub-base or manifold block" in this chapter.
5-19