7.2.6 Synchronizing possibilities

Synchronizing
possibilities
Sync signals for
BASE- and
COM BOARD
Hardware - SIMADYN D
Edition 03.2001
HongKong|UK|China
www.aotewell.com
The T400 offers various ways to process and transfer synchronizing signals.
The processing possibilities are listed in the following diagram. The three
selector switches indicated, are set by appropriate configuring.
Inputs
Com board
X2 / A26
L_INT_DPR_PT
Base board
X1 / B25
L_INT_CU_DPR
Fig. 7-4 Synchronizing possibilities
The basic cycle of the T400 can be taken from three various sources (can
be configured in HWConfig):
• Basic cycle time of the T400 (standard)
• Synchronizing signal of the BASE BOARDs (L_INT_CU_DPR (connector
X1/B25) for T0GATE)
• Synchronizing signal of the COM BOARDs (L_INT_DPR_PT (connector
X2/A26) for T0GATE)
Thus, a cycle from the CBX can synchronize the T400 and BASE BOARD
(CU).
Configurable interrupt tasks can also be called using the synchronizing
signals from BASE- or COM BOARDs (ports A/4, A/5).
The T400 can supply BASE- and COM BOARD synchronizing signals, which
come from the following three sources and can be selected by appropriately
configuring:
• Basic cycle time of the T400 (T0OUT of MFB1)
• Directly connecting synchronizing signals from the BASE- or COM
BOARD to the other module
• In an FP with a special FB-generated synchronizing signal
(SYNC_BASE, SYNC_COM)
sales@aotewell.com
Steer
Processor
Port A/4
SYNC_COM
T0GATE
T0OUT
Port A/5
SYNC_BASE
Industry Automation
Technology subrack
Outputs
Com board
X2 / B25
L_INT_PT_DPR
Base board
X1 / A26
L_INT_DPR_CU
7-9