24
SYSTEM ERROR
INIT. ERROR, NO
25
MEASURED VALUE
INIT. DATA
26
INIT. ERROR, NO
BINARY VALUE INIT.
DATA
27
INIT. ERROR,
MEASURED VALUE
INIT. DATA
28
INIT.ERROR, BINARY
VALUE - INIT. DATA
29
MEASURED VALUE
CHANGE ERROR
30
INITIALIZATION ERROR,
DELAY
31
INTERRUPTION TO THE
HOST CONNECTION
32
NO BUS CONNECTION,
INCORRECT STATION
ADDRESS
33
PRINTER NOT READY
OR NOT CONNECTED
35
EPROM SAVE
UNSUCCESSFUL
36
TELEGRAM ERROR, NO
BUS CIRCULATION

Operating messages

Information texts, alarms (warnings) and fault/error messages are displayed
as operating messages for approximately three seconds, in order to support
the operator resolve problems.
sales@aotewell.com
Operator control panel OP2
Description /cause/ corrective
action
- defective BUS cable
Device not able to function. Critical
faults/errors in the electronics.
Process data haven't been
completely initialized. OP2 expects
additional process initialization
data. OP2 is not ready. Check the
BUS structure and configuring.
Process data haven't been
completely initialized. OP2 expects
additional process initialization
data. OP2 is not ready. Check the
BUS structure and configuring.
The initialization data for the
process data are erroneous. The
OP2 is not ready. Check the BUS
structure and configuring
The initialization data for the
process data are erroneous. The
OP2 is not ready. Check the BUS
structure and configuring.
Error when changing the process
data. Changing process data in the
VAL/CHANGE mode was
unsuccessful. Repeat the function,
if required check configuring.
Initialization time monitoring
(watchdog) exceeded. OP2 not
ready. Check the BUS structure
and configuring.
No USS telegrams are received.
Check the BUS connection/cable.
No telegrams with their own
particular station address received.
Configuring error or BUS address
incorrectly set.
OP 2 does not print. The printer
does not respond. Check the
printer and printer cable.
Saving the VAL/CHG/ mode in the
EPROM unsuccessful, check
configuring.
Check the BUS structure, check
the configuring, master is not
transmitting SCAN telegram with
the OP node number.
Industry Automation
Reference
(Chapter)
General
information
2.3
2.3
2.3
2.3
1.2.3
2.3.2
2.2
2.2 + 1.5.4
1.4.6
1.2.3
10
2.2
10-21