Input/output modules
Coding plug
NOTE
WARNING
!
5-18
www.aotewell.com
The signal voltage is selected, i. e. the associated receive driver is
connected by inserting 2 coding plugs, lying one behind the other, into a
certain setting (also refer to the following diagram).
If the coding plug is used so that the closed wire jumper is towards the front
panel of the IT41, then a 5V encoder has been selected.
If the interrupted jumpers point towards the front panel, a 15V encoder has
been selected. This is the factory setting.
15V encoders with separate forwards/reverse tracks cannot be used
without any further measures.
Front panel
X100
X6
X200
X300
X400
X7
Fig. 5-4 Assignment of the coding plug for incremental encoders
If coding plugs are incorrectly inserted, the inputs could be destroyed
when pulses are input!
sales@aotewell.com
X101
Configured for 5 V encoders
(e. g. SONY)
X201
X301
Configured for 15 V encoders
X401
(Component side IT41)