Technical Data - Siemens SIMADYN D Hardware Manual

Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

Subracks
2.1.7

Technical data

Input voltages
Output voltages
2-8
www.aotewell.com
AC power supply according to DIN IEC 38
Input voltage V in
Input frequency
Non-periodic overvoltages according to DIN VDE160, A5.3.1.1.2
Voltage
Duration
Recovery time, min
Events per hour
Brief voltage dips according to DIN VDE 0160, A5.3.1.1.3
Voltage
Duration
Recovery time, min
Events per hour
Output voltage 5 V
Output current
Ripple
Commutating spikes
Base load
Overvoltage protection
Stabilization time
Output voltage +15 V
Output current
Ripple
Base load
sales@aotewell.com
230 V (+ 10% / - 15%)
47.5 ... 62.5 Hz
460 V
1.3 ms
0.1 s
max. 10
0
5 ms
0.1 s
max. 10
+5.1 V +/- 0.1 V
1.5 to 7 A
< 50 mV pp
< 5% (of 5V)
1.5 A
when a CPU module is inserted
with suppressor diode
to protect the modules
< 80 ms after V in = 230 V;
<1 ms
after load step (0.5 ->1)*I rated
+15 V +/- 0.3 V
0 to 0.7 A
< 150 mV pp
Guaranteed by an inserted module
which requires this voltage
Hardware - SIMADYN D
Industry Automation
Edition 04.2011
+86-755-8660-6182

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents