6.2.1 Application information and noise immunity

Other information

6.2.2 Connector assignment of the interfaces

Parameterizing
interface X5
Hardware - SIMADYN D
Edition 12.2004
HongKong|UK|China
www.aotewell.com
The CP1470 can be reset using the reset button. The switch must first be
set to "ADM".
Green Red
Significance
Dark
Dark
No power supply;
temporary initialization status
Lit
Dark
Database and synchronization O.K.
Flashi
Dark
Database inconsistent; correct NML configuring
ng
Dark
Lit
No synchronization with the initializing CPU module;
possible cause: @CSH11 function block not configured,
incorrect slot or incompatible firmware
Dark
Flashin
Hardware fault
g
Flashi
Lit
Switch in the STOP setting or ADM
ng
The function of the LEDs is also described in the User Instructions
„Configuring the communications".
• the module may only be used in forced-ventilated subracks.
• the serial connecting cables must be latched-in using the latching
mechanisms provided.
• noise-immune operation is only possible if the module is tightly screwed
into the subrack
Further information on EMC and ambient conditions, refer to Section
„General technical data".
25-pin sub D socket connector
Pin
RS-232
TTY
1
Screen
----
2
TxD
----
3
RxD
----
7
Ground
----
9
----
+RxD
10
----
-RxD
18
----
+TxD
21
----
-TxD