5.1.4 Technical data

General data
Power supply
Analog outputs
Hardware - SIMADYN D
Edition 12.2004
HongKong|UK|China
www.aotewell.com
The front panel and if relevant, a connector housing, initially have no contact
to the electronics ground of the module. The front panel is only connected to
the electronics ground of the module via the backplane bus connector (L/C
bus connection) and a cable connection, which can be released, between
the backplane bus and the subrack housing.
Further information on EMC and ambient conditions, refer to Section
"General technical data"
No. of slots occupied
Dimensions W x H x D [mm]
Weight
Rated voltage
min.
+5 V
+4.75 V
+15 V
+14.4 V
-15 V
-15.6 V
No.
Output voltage, min.
Output voltage, max.
Output current
Output current (at +/- 10 V)
Resolution
Accuracy
Short-circuit protection to ground
Short-circuit duration
Total load
Temperature dependency
Error
absolute linearity
differential linearity
monotony
sales@aotewell.com
Input/output modules
1
20.14 x 233.4 x 220
Approx. 0.5 kg
max.
Typ. current drain
+5.25 V
600 mA
+15.6 V
200 mA
-14.4 V
200 mA
8
- 10 V
+ 10 V
+/- 10 mA max.
+/- 5 mA
(recommended to suppress noise)
13 bits + sign (corresponds to 1 mV)
14 bits (corresponds to 1 mV)
With 56 Ohm resistor
120 s
All outputs simultaneously, each 10 mA
Max. 240 μV/degrees
+/-0.6 mV
+/- 1 mV
14 bits (corresponds to 1 mV)