Technical Data - Siemens SIMADYN D Hardware Manual

Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

Input/output modules

5.4.7 Technical data

General data
Power supply
Integrating analog
inputs
Sampling analog
inputs
5-42
www.aotewell.com
No. of slots occupied
Dimensions W x H x D [mm]
Weight
Rated voltage
min.
+5 V
+4.75 V
+15 V
+14.4 V
-15 V
-15.6 V
24 V (external)
20 V
No.
Integrating analog inputs
Integration time
Input voltage range
Input resistance
Input filter
Resolution
Relative accuracy
No.
Type
Input voltage range
Input resistance
Input filter
Resolution
Absolute accuracy
Max. conversion time
sales@aotewell.com
1
20.14 x 233.4 x 220
Approx. 0.5 kg
max.
Typ. current drain
+5.25 V
420 mA
+15.6 V
450 mA
-14.4 V
140 mA
30 V
100 mA + binary output currents
4
Differential inputs, floating, V/f conversion
sampling time of the AFC function block or
the time between 2 positive edges of the
external trigger signal
-10 V to +10 V
470 kOhm
-3 dB transition frequency : 2 kHz
Up to 17 bits, depending on the integration time:
13 bits at 1 ms integration time
15 bits at 4 ms integration time
17 bits at 20 ms integration time
Typ. 14 bits
4
Differential inputs, non-floating
-10 V to +10 V
470 kOhm
-3 dB transition frequency : 1.5 kHz
12 bits
Typ. 10 bits over the complete temperature
range
45 µs.
Industry Automation
Hardware - SIMADYN D
Edition 12.2004
+86-755-8660-6182