Technical Data - Siemens SIMADYN D Hardware Manual

Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

Technology subrack
Analog input 2
Ground, analog inputs and outputs
Note:
Grounding

7.2.9 Technical data

General data
Power supply
7-12
www.aotewell.com
All grounds are connected mutually via inductivity and with electronics
ground.
The grounds connections of
interfaces 1 and 2
analog inputs/outputs
binary inputs/outputs.
incremental encoders 1 and 2
are connected to the T400 electronics ground through 0 Ohm resistors,
reactors and capacitors which can be soldered-out. For production-related
reasons, the 0 Ohm resistor is an SMD device (not separately connected)
and when required must be soldered-out (to interrupt the electrical
connection)!
No. of slots occupied
Dimensions W x H x D [mm]
Weight
The T400 requires the following voltages at the upper backplane bus
connector X1:
Rated voltage
min.
+5 V
+4.75 V
+15 V
+14.4 V
-15 V
-15.6 V
24 V (external)
20 V
sales@aotewell.com
1
20.14 x 233.4 x 220
approx. 0.6 kg
max.
Typ. current drain
+5.25 V
1000 mA
+15.6 V
140 mA + encoder load
(max. 100 mA, electronically limited)
-14.4 V
140 mA
30 V
150 mA + binary output current