Operator control panel OP2
10-22
www.aotewell.com
No Text
MEASURED VALUE NOT
1
INITIALIZED
2
FUNCTION NOT
PERMISSIBLE
3
UPPER LIMIT
EXCEEDED
4
LOWER LIMIT FALLEN
BELOW
5
SETPOINT CHANGE
INHIBITED
6
LAST CHANGE STILL
NOT ACCEPTED
7
DELAY TIME EXPIRED
8
FUNCTION NOT
POSSIBLE
9
INCORRECT INPUT
11
INITIALIZATION
RUNNING
12
MEASURED VALUE
INITIALIZATION
13
BINARY VALUE
INITIALIZATION
14
NO MEASURED VALUE
INITIALIZED
15
NUMBER OF LOST
MESSGES:
17
NO FURTHER
MESSAGES PRESENT
sales@aotewell.com
Description /cause/ corrective
action
A process data number V1..V24
was selected which was not
configured in SIMADYN D
This function is not permissible in
this mode.
The configured upper limits were
exceeded when a setpoint was
entered or changed.
The configured lower limit was
fallen below when entering a
setpoint or changing it
When selecting the change mode
for a process data, SIMADYN D
did not enable the change.
Presently occupied/changed by
another OP or, was configured as
ACT value.
SIMADYN D did not accept the last
process data change. Repeat the
function or check the configuring.
SIMADYN D has still not accepted
the actual process data change.
The monitoring time (watchdog)
exceeded. Repeat the function or
check the configuring.
A key was depressed which is not
possible in the current mode.
An invalid value has been entered
OP2 waits for general INIT DATA.
OP2 not ready, if required, check
BUS structure and configuring.
OP2 waits for process data
initialization. OP2 not ready, if
required check BUS structure or
configuring.
OP2 waits for BINARY VALUE
initialization. OP2 not ready, if
required, check BUS structure or
configuring.
No process data were initialized
and configured, VAL function is not
possible
Message processing overflow
message. This message is entered
into the message buffer as the
latest message. The most recent
messages overwrite the oldest
messages. The number of lost
messages is incremented until
messages are deleted using DEL.
The end of the messages has been
reached when scrolling through the
message buffer.
Industry Automation
Reference
(Chapter)
1.2
General
information
1.2
1.2
1.2
1.2
1.2
General info
General info
2.2.1
2.2.1
2.2.1
1.2
1.4
1.4
Hardware - SIMADYN D