indicate the operating status and alam condition of the UPS system. The
Figure 32
shows the relay interface module, with its fOUr 1 s-pin connectors Ikbeled Ji
Drawing le42002%-13 On Ps9e A-23 Outlines the enclosure dimensions,
J4.
CONNECTORS
To install an RIM:
mount the RIM.
1. Securely
2. Install wiring from the RIM through l/2" conduit and through the l/2" knockout
in either the top or the bottom of the UPS cabinet.
The top entry connection requires installation of l/2" flexible conduit within the
UPS. Bottom entry connection requires no additional routing of conduit within
the UPS.
3. In the hardware kit, locate the terminal block (see Figure Xi). Plug the
connector on the back of the terminal block into the DE-9 conrrector on the
Communications Panel of the UPS (see Figure 34). Use two screws from the
hardware kii to secure the terminal block plate to the Communications Panel.
Relay Interface Module
to eight criticsl loads.
FLUSH MOUNT