This UPS system is housed'in freestanding. double front cabinets with
safety shields behind the doors. The UPS is available in
ratings, in both 50 and 60 Hz models. Smaller models may be field-upgraded to larger
output power ratings:
50 Hz Systems:
40 kVA, 32 kW maxirrium (upgradeable to 50 kVA or 65 kVA)
50 kVA. 40 kW maximum (upgradeable to 65 kVA)
66 kVA. 52 kW maximum
60 Hz Systems:
50 kVA, 40 kW maximum (upgradeable to 65 kVA or 80 kVA)
80 kVA, 84 kW maximum
The following sections detail the input, output, environmental, and battery specifications for
this UPS.
System Input
Input Current
Input Currsd Hsmmnic
content
Power Factor
Plus 80 UPS Operator's Manual
Suitable for use on 35OV, 4OOV, and
480 VAC for operation from 400 VAC to 528 VAC
Suitable for use on 200'4 208V, and 220V systems
125% of full load for ovehad + battety charge
Actual load + 25% of full load for battery charge
Adjustable, set to 102%
THD at full load
Typically 15-20 second rectifier ramp-up to full
Minimum 0.g
8
4 1