Keep these notes in mind while installing the UPS:
I
I
I
I
I
I
I
I
I
I
I
I
12
Dimensions in this book are in millimeters (inches).
l
Do not tilt the UPS or other cabinets more than 210' during installation.
l
Coolind exhaust airffow is approximately 614.0 US (1300 CFM).
l
The condutt landing plates are to be removed, to add conduit landing holes
l
as required. Plate material is 16 gauge steel (O6 inches thick).
Terminals El - El 5 are UL and CSA rated at WC. A hex key tool is
l
required to attach wires to the terminals.
The remote Emergency Load Cff feature opens all breakers and contactors
l
in the UPS cabinet and isolates power from your critical load. Local
If perforated floor tiles are required for ventilation, place them in front of the
l
UPS. The weight and point loading of the UPS cabinet are: (
Maximum WeigM
6 at 200 kg (440 Ibs) with casters
4 at 200 kg (662 Ibs) without casters
Details about control wking are provided in each procedure for connecting
l
options and features. Table N on page A-4 identifies the control wiring
terminations.
Plus 80 UPS lnstaflation Manual
l :