Operational info collection
18.2.

Event report

Information
18.3.

Characteristics

18.3.1.

Torque profile characteristics

Properties
Conditions
Information
108
Indication on display
Av. temp mot. (user)
Max. temp. MWG
Min. temp. MWG
Temp mean value MWG
Av. op.time OPEN user
Av. op. time CL user
Wrn hi temp log. user
Wrn lo temp log. user
Wrn hi temp mot. user
Wrn lo temp mot. user
Last op.time CL user
Last op. time OP user
Last op.time ref CL user
Last op.time ref OP user
Reset operating data
Required user level: Specialist (4) or higher.
Operational info collection M1231
Operational info M0177
Reset operation. info M0197
The entries in the operating data logging can be reset (deleted) via this menu.
The event report records system events and status signals. The event report can be
exported to the external SD card or read via AUMA CDT software or the AUMA
Assistant App. This allows e.g. comparisons of previous operations of actuator and
valve.
Since the events are recorded with a time stamp, date and time (parameter Date
and time M0221) should be properly set.
Two different torque profile operations can be performed:
Reference operation
Comparative operation
Parameter Torque profile M2427 must be configured and may not be set to
None.
Operation mode OFF
User level: Specialist (4) or higher.
Torque profiles or characteristics can be easily adopted into and visualised within
the AUMA CDT software using the respective button.
Operational info collection M1231
Characteristics M0313
Torque profile M2901
Reference and comparative operations can be aborted using the STOP command.
Description
Average temperature of motor
Maximum temperature of the MWG
Minimum temperature of the MWG
Mean value of temperature information on the MWG sub-as-
sembly
Mean value of operating time OPEN (user)
Mean value of operating time CLOSE (user)
Warning time excessive temperature logic (user)
Warning time insufficient temperature logic (user)
Warning time excessive temperature motor (user)
Warning time insufficient temperature motor (user)
Last operating time in operation direction CLOSE (user)
Last operating time in operation direction OPEN (user)
Last operating time reference operation in direction CLOSE
(user)
Last operating time reference operation in direction OPEN
(user)
Multi-turn actuators